Design Requirements: Difference between revisions
Jump to navigation
Jump to search
(7 intermediate revisions by the same user not shown) | |||
Line 6: | Line 6: | ||
** 2-4 Form C relays for alarm, other functions (5A rating) | ** 2-4 Form C relays for alarm, other functions (5A rating) | ||
* Real-time clock accurate to +/- 20ppm | * Real-time clock accurate to +/- 20ppm | ||
** Consider temperature stability of quartz crystal (AT cut vs tuning fork) | |||
** Battery backup for date/time | ** Battery backup for date/time | ||
* Allow for 4 Wiegand Readers | * Allow for 4 Wiegand Readers | ||
Line 20: | Line 21: | ||
* On-board RS-485 support | * On-board RS-485 support | ||
==== Expansion Capability ==== | ==== Expansion Capability ==== | ||
* Provision for Ethernet (4xSPI pins) | * Provision for Ethernet (4xSPI pins) | ||
* Additional SPI select pins available | |||
* Provision for SD card support | * Provision for SD card support | ||
* Provision for external host-mode USB support | * Provision for external host-mode USB support | ||
* Break-out of all pins, including ICSP | * Break-out of all pins, including ICSP | ||
==== Power ==== | ==== Power ==== | ||
* 12-14VDC operation | * 12-14VDC operation | ||
* Voltage-divided analog inputs for monitoring input voltage | |||
* Optional analog or digital input for monitoring external PSU voltage | |||
** Adaptable to 24V with component changes | ** Adaptable to 24V with component changes | ||
* On-board switching PSU for 5V or 3.3V needs | * On-board switching PSU for 5V or 3.3V needs | ||
Line 40: | Line 44: | ||
==== Physical ==== | ==== Physical ==== | ||
* 4x6" form-factor | * 4x6" form-factor | ||
* 4 #6 mounting screws | |||
* Arduino mounting screws | |||
* Double-sided, SMT design | * Double-sided, SMT design | ||
* 3.5mm screw terminals (~60 count) | * 3.5mm screw terminals (~60 count) | ||
Line 47: | Line 53: | ||
** 2 pins for power input | ** 2 pins for power input | ||
** 8 pins for power distribution (optional) | ** 8 pins for power distribution (optional) | ||
=== Environmental === | |||
* Working temperature range from -25 to 55C | |||
* Design towards FCC Class B | |||
** Only when used with metal case | |||
* Immunity | |||
** 2500V standard |
Latest revision as of 14:43, 12 November 2011
Specifications for Open Access 3.0 Hardware
General
- Based on Arduino Mega 2560 Microcontroller
- Control at least 4 doors
- 4 Form C relays for doors (5A rating)
- 2-4 Form C relays for alarm, other functions (5A rating)
- Real-time clock accurate to +/- 20ppm
- Consider temperature stability of quartz crystal (AT cut vs tuning fork)
- Battery backup for date/time
- Allow for 4 Wiegand Readers
- 6-pin format to allow control of LED/Beeper
- PWR,GND,1,0,LED,BEEP
- Allow for wide range of pulse widths
- 20-400uS pulses from logic high to GND
- 6-pin format to allow control of LED/Beeper
- 8+ Supervised alarm zones
- 4-state supervision
- Detect faults such as zone cut/broken, short
- Detect closed and open states
- 2-terminal design
- Include current limiting and ESD protection
- 4-state supervision
- On-board RS-485 support
Expansion Capability
- Provision for Ethernet (4xSPI pins)
- Additional SPI select pins available
- Provision for SD card support
- Provision for external host-mode USB support
- Break-out of all pins, including ICSP
Power
- 12-14VDC operation
- Voltage-divided analog inputs for monitoring input voltage
- Optional analog or digital input for monitoring external PSU voltage
- Adaptable to 24V with component changes
- On-board switching PSU for 5V or 3.3V needs
- Input power protection
- Reverse polarity protection
- Surge and ESD protection
- Fused input rail
- External power rails
- Polyfuses or fuses for additional power outputs
- Can be on-board or on separate power distribution board
Physical
- 4x6" form-factor
- 4 #6 mounting screws
- Arduino mounting screws
- Double-sided, SMT design
- 3.5mm screw terminals (~60 count)
- 24 terminals for 4x6-pin Wiegand inputs
- 16 terminals for 8x2-pin alarm inputs
- 18 terminals for 6x3-in relay outputs
- 2 pins for power input
- 8 pins for power distribution (optional)
Environmental
- Working temperature range from -25 to 55C
- Design towards FCC Class B
- Only when used with metal case
- Immunity
- 2500V standard